OMRON | Mitsubishi
Home >> Download >> MITSUBISHI >> FX Series PLC >> mitsubishi FX0N mitsubishi_FX0N-3A USER'S GUIDE
mitsubishi FX0N mitsubishi_FX0N-3A USER'S GUIDE
Introduction:

. Connection with PLC
1) Up to 4 FX 0N-3A units can connect to the FX0N series PLC, up to 5 for FX 1N, up to 8 for FX2N or, up to
4 for an FX 2NC series PLC, all with powered extension units.
However the following limitation exists when the undermentioned special function blocks are con-nected.
FX2N: Main unit and powered extension units of 32 I/O points or less. Consumption current available for
undermentioned special function blocks ≤ 190mA
FX2N: Main unit and powered extension units of 48 I/O points or more. Consumption current available
for undermentioned special function blocks ≤ 300mA
FX2NC : Up to 4 undermentioned special function blocks can be connected regardless of the system I/O.
FX0N/1N : Main unit and powered extension units. Up to 2 undermentioned special function blocks can be
connected regardless of the system I/O.
The consumption current of the above units is to be subtracted from the service power supply of the host
PLC.
2) FX0N-3A consumes 5V DC by 30mA. The total 5V consu