Pressure Sensors

What Are Pressure Sensors?


A pressure sensor is a device equipped with a pressure-sensitive element that measures the pressure of a gas or a liquid against a diaphragm made of stainless steel, silicon, etc., and converts the measured value into an electrical signal as an output.
 


Operating Principles


A semiconductor piezo-resistance dispersion pressure sensor has a semiconductor distortion gauge formed on the surface of the diaphragm, and it converts changes in electrical resistance into an electrical signal by means of the piezo-resistance effect that occurs when the diaphragm is distorted due to an external force (pressure).

A static capacitance pressure sensor has a capacitor that is formed by a static glass electrode and an opposing movable silicon electrode, and it converts changes in static capacitance that occur when the movable electrode is distorted due to an external force (pressure) into an electrical signal. (The E8Y uses the static capacitance method, and other models use the semiconductor method.)


Semiconductor Distortion Gauge Construction


Semiconductor Distortion Gauge Construction



Piezo-resistance Effect


Piezo-resistance Effect

The electrical resistance of the above conductor is expressed by the following formula:
R = L/S.

When this conductor is pulled to the right or left as shown below, the length increases and the cross-sectional area decreases.
Diagram illustration

The electrical resistance of the above conductor is expressed by the following formula:
R' = (L+1)/S-s.

Accordingly,
R' > R.
This shows how the application of a mechanical force changes the electrical resistance.
 



Explanation of Terms


Gauge Pressure


The amount of pressure is expressed in terms of atmospheric pressure. It is referred to as "positive pressure" when it is greater than one atmosphere, and "negative pressure" when it is less than one atmosphere.


Absolute Pressure


This is the amount of pressure expressed in relation to an absolute vacuum.


Pressure Difference (Relative Pressure)


This is the amount of pressure compared to any particular pressure (the reference pressure).

Pressure Difference (relative pressure)


Atmospheric pressure


The pressure of the atmosphere. The standard atmospheric pressure (1 atm) is equal to the pressure of a column of mercury with a height of 760 mm.


Vacuum


A pressure less than one atmosphere.


Pressure Detection Range


The range of pressure that can be detected by the Sensor.


Withstand Pressure


The pressure that must be withstood without degraded performance after returning to the pressure detection range.


Repeat Accuracy (ON/OFF Output)


Repeat accuracy refers to the deviation in the operating point when the output inverts while pressure is increased or decreased at a temperature of 23C, divided by the full scale of the pressure detection range.

Formula for Repeat Accuracy
 


Accuracy (linear)


This is the deviation from the rated output current (4 mA, 20 mA) when zero pressure and the rated output are applied at a temperature of 23C, divided by the full-scale value.

It is expressed in units of %F.S.


Linearity


The analog output changes in an approximately linear fashion with respect to the detected pressure. The change, however, deviates slightly from an ideal straight line. This deviation is expressed as a percentage of the full scale.

Linearity



Linear Hysteresis


An ideal straight line is drawn between the output current (or voltage) at zero pressure and the rated current (or voltage), and the difference between the measured current (or voltage) and the ideal current (voltage) is obtained as an error. The error as the pressure rises and the error as the pressure falls are obtained, and the maximum value of the absolute value of the difference between the rising error and falling error is divided by the full scale current (or voltage). This is the linear hysteresis, and it is expressed in units of %FS.


Hysteresis (ON/OFF Output)


The difference between the output ON pressure and OFF pressure is divided by the full pressure scale.

Hysteresis formula and graph
 


Non-corrosive Gas


Substances contained in the air (nitrogen, carbon dioxide, etc.) and inert gases (argon, neon, etc.).


Measurement Method


A new Measurement Law was enacted in Japan on November 1, 1993. This law prohibits the use of Torr for anything except internal human body pressure measurements. From September 30, 1999, the use of kgf/m², mHg (except for blood pressure measurements), and mH2O was prohibited.


Pressure Unit Conversion Table

 

 

kgf/cm²

mmHg

mmH2O

Pa

1kgf/cm²

1

735.559

1.000028 x 104

0.0980665M

1mmHg

1.3595 x 10-3

1

1.3595 x 10

0.133322k

1mmH2O

0.99997 x 10-4

7.356 x 10-²

1

0.00980665k

1Pa(N/m2)

1.0197 x 10--5

7.5006 x 10-3

0.10197

1

Output Impedance


1. Measuring the Output Impedance of Voltage Output Models


Figure 1

Measuring the Output Impedance of Voltage Output Models


Ro : Output impedance
Rx : Load resistance
Eo : Output voltage (terminals open)
Ex : Output voltage (with load Zx connected)
Ix : Load current (with load Zx connected)


In Figure 1, the current (Ix) that flows when the load resistance (Rx) is connected is calculated as follows:

Formula for load resistance (Rx)

The output impedance (Ro) in Equation (1) is calculated as follows:

Formula for output impedance (Ro)

The voltage (Eo) is measured when the output is open, followed by the voltage (Ex) when a load resistance (for example, the minimum value of the permitted load resistance of a transducer) is connected.


The measured values Eo and Ex and the connected load resistance (Rx) are inserted into Equation 2 to calculate the output impedance (Ro) of the transducer.


2. Measuring the Output Impedance of Current Output Models


In Figure 2, the voltage (Ex) of the output terminals when the load resistance (Rx) is connected is calculated as follows:

Formula for Voltage (Ex)

The output impedance in Equation (3) is calculated as follows:

Formula for Output Impedance (Ro)

Here, the current (Io) is measured with the output short-circuited.

Figure 2


Circuit diagram

Ro : Output impedance
Rx : Load resistance
Io : Output current (output terminal short-circuited)
Ix : Output current (with load Rx connected)
Ex : Output voltage (with load Rx connected)

Next, the output current (Ix) is measured when a load resistance (for example, the maximum value of the permitted load resistance of a transducer) is connected. The measured values Io and Ix and the value of the connected load resistance (Rx) are inserted into Equation 4, and the output impedance (Ro) of the transducer is calculated. The output impedance of the transducer introduced here is the value for normal operation.


3. Desirable Output Impedance


In general, it is best to make the output impedance of a voltage output transducer as small as possible, i.e., as close to 0 W as possible, to minimize the effects of load fluctuations on the transducer. For a current output transducer, the opposite is true: the higher the impedance (the closer to infinite impedance), the better.


4. Example of Calculation Using Impedance

Error in analog voltage output's formula
 

Rx

Error

1k

Approximately 10%

10

Approximately 1%